Last reviewed: 2026-07-11 · Certified Fire Doorsets technical team · Sources cited below
BS 476-22 and BS EN 1634-1 are the two fire door fire-resistance tests accepted in England. BS 476-22 underpins FD ratings (FD30, FD60); EN 1634-1 results are classified to BS EN 13501-2 (E30, EI30, with Sa/S200 smoke classes). Approved Document B currently accepts both, but removes the BS 476 fire resistance classes from 2 September 2029.
- From 2 September 2029, BS 476 fire resistance classes are removed from Approved Document B in England, leaving BS EN 1634-1 with BS EN 13501-2 as the sole route.
- FD30 broadly corresponds to E30, and FD30s to E30 with an Sa or S200 smoke class, under BS EN 13501-2.
- EI is stricter than E or FD: it adds an insulation criterion limiting the mean temperature rise on the unexposed face to 140°C.
- The EN 1634-1 furnace delivers more heating energy in the early stages of the test; industry reporting suggests a 5-20% reduction in measured performance versus BS 476-22.
- The neutral pressure plane sits at 500mm in EN 1634-1 against 1000mm in BS 476-22, forcing more hot gas at the door head.
- Existing BS 476-tested fire doors do not need replacing: Approved Document B guidance applies to new building work, not doors already in service.
Why are there two fire door testing standards in the UK?
A fire door only earns its rating through a furnace test on a full-size doorset. In England, two test standards have run side by side for decades: BS 476-22, the national fire resistance test dating from 1987, and BS EN 1634-1, the European test whose results are classified under BS EN 13501-2. The BWF Fire Door Alliance confirms that fire resistance is determined by testing full-sized constructions to "the appropriate fire test standard, BS 476: Part 22 or BS EN 1634-1" at UKAS-accredited laboratories.
Approved Document B — the statutory guidance supporting the Building Regulations 2010 in England — currently accepts either route for fire resistance. That dual system is ending. The government has confirmed a phased withdrawal of the national BS 476 classes, and the fire resistance stage takes effect on 2 September 2029. Understanding both regimes, and how FD ratings map onto E and EI classes, is now essential for anyone specifying, buying or approving fire doorsets.
How do the BS 476-22 and EN 1634-1 tests differ?
Both tests mount a complete doorset in a supporting construction in front of a furnace that follows the standard time-temperature curve, then observe how long the assembly holds back flames and hot gases. The differences lie in how the furnace is instrumented and pressurised — and they matter, because the European method is generally the more punishing of the two.
| Aspect | BS 476-22 (national) | BS EN 1634-1 (European) |
|---|---|---|
| Furnace thermocouples | Unshielded probe thermocouples, quick to respond | Shielded plate thermocouples, slower to respond, so the furnace delivers more heating energy early in the test |
| Neutral pressure plane | 1000mm above the notional furnace floor | 500mm above the notional furnace floor, increasing positive pressure at the door head |
| Effect at the door head | Lower pressure on the top of the doorset | More hot gas driven through the head, top seals and upper hinges |
| Output | FD rating: FD30, FD60, FD90, FD120 ('s' suffix for smoke control) | Classification to BS EN 13501-2: E, EW or EI plus optional Sa/S200 smoke classes |
| Field of application | National conventions and assessments define what variations the evidence covers | Formal direct and extended field of application rules define permitted variations from the tested specimen |
| Status in Approved Document B (England) | Accepted for fire resistance until 2 September 2029 | Accepted now and becomes the sole classification route from 2 September 2029 |
The BWF Fire Door Alliance explains the two headline differences: BS 476-22 uses unshielded thermocouples while "EN 1634-1 uses shielded thermocouples which are less responsive to changes in temperature, resulting in increased heating energy" early in the test, and "the neutral pressure plane is positioned lower in BS EN 1634-1 tests (500mm from the notional furnace floor level, compared to 1000mm in BS 476-22)". Industry testing experience, summarised by UK Testing & Certification, suggests these differences produce roughly a 5-20% reduction in measured performance when the same doorset design is tested to EN 1634-1 rather than BS 476-22.
The practical consequence: a doorset that passes EN 1634-1 will almost certainly satisfy the BS 476-22 criteria, but the reverse cannot be assumed. A BS 476-22 test report cannot simply be converted into an EN classification — demonstrating an E or EI class requires EN test evidence.
What do E, EI and EW mean under EN 13501-2?
BS EN 13501-2 is the classification standard that turns EN 1634-1 test data into a class. For fire doors, three performance criteria matter — integrity (E), insulation (I) and radiation (W) — and each class carries a number giving the minutes achieved.
E — integrity only
An E-classified door prevents the passage of flames and hot gases for the stated period, judged by criteria such as sustained flaming on the unexposed face, gap gauges and ignition of a cotton pad. It does not limit how hot the unexposed face becomes, so combustible materials close to the door could still ignite from transmitted heat. E30 and E60 are the nearest European counterparts to FD30 and FD60, because FD ratings are also integrity-based.
EI — integrity plus insulation
An EI-classified door satisfies the integrity criteria and additionally limits heat transfer through the doorset: the mean temperature rise on the unexposed face must not exceed 140°C for the classified period. Two variants exist — EI1 and EI2 — which differ in where thermocouples are placed near the edges and frame and in the maximum local rises permitted; EI1 is the stricter of the two, and EI2 is the variant normally used for doorsets. EI classifications are typically specified where people could be close to the door for a sustained period — protected stairways and lobbies in taller residential buildings, sleeping accommodation, and specifications written to BS 9991:2024 or project fire strategies that demand insulation performance.
EW — integrity plus radiation control
An EW-classified door satisfies integrity and also limits radiated heat, which as EBD Steel Doors summarises, "limits the radiant heat transfer to below 15 kW/m2 at a measured distance from the door" (measured 1m from the unexposed face). EW sits between E and EI: it protects people passing the door from radiant heat without providing full insulation. It appears more often in European specifications than in UK ones, but you will increasingly meet it on internationally specified projects.
Sa and S200 — the smoke classes
Smoke control is tested separately (BS EN 1634-3) and expressed as Sa — smoke leakage limited at ambient temperature only — or S200 — leakage limited at both ambient temperature and 200°C, the medium-temperature condition. These are the European counterparts of the UK's 's' suffix: FD30s broadly corresponds to E30 Sa or E30 S200, with the class chosen by the specification. Smoke-classified doorsets need effective smoke seals and controlled threshold gaps, exactly as an FD30s door does.
FD ratings to EN classifications: the mapping table
The table below gives the accepted working equivalence between the national FD ratings and the European classes. Treat it as indicative, not as a conversion: because the EN test is generally more onerous, an FD-rated design must still hold EN test evidence before it can claim the corresponding E class.
| BS 476-22 rating | Nearest EN 13501-2 class | Performance | Notes |
|---|---|---|---|
| FD30 | E30 | 30 minutes integrity | Typical leaf thickness 44mm |
| FD30s | E30 Sa or E30 S200 | 30 minutes integrity plus smoke control | Smoke class set by the specification; requires smoke seals |
| FD60 | E60 | 60 minutes integrity | Typical leaf thickness 54mm |
| FD60s | E60 Sa or E60 S200 | 60 minutes integrity plus smoke control | Common for protected shafts and riser access in taller buildings |
| FD90 | E90 | 90 minutes integrity | Specialist doorsets, often steel or heavy timber composite |
| FD120 | E120 | 120 minutes integrity | Specialist doorsets for high-hazard or compartment-line locations |
| No FD equivalent | EI30 / EI60 / EI90 / EI120 | Integrity plus insulation (140°C mean rise limit) | Stricter than any FD rating; needs EN test evidence classified EI |
| No FD equivalent | EW30 / EW60 | Integrity plus radiation control (15 kW/m² at 1m) | Between E and EI; more common in European specifications |
Two rules of thumb follow. First, when reading an EN classification, the letters tell you what is controlled and the number tells you for how long. Second, when comparing routes, equivalence only ever runs FD-to-E: there is no FD rating that demonstrates EI or EW performance.
What does Approved Document B currently accept?
As of mid-2026, Approved Document B in England accepts fire resistance demonstrated by either the national route (BS 476-22, FD ratings) or the European route (BS EN 1634-1 classified to BS EN 13501-2). For reaction to fire — surface linings, not fire doors — the national classes (Class 0, Class 1) have already been removed: that change took effect on 2 March 2025.
The government's amendment circular sets out the full phased timetable, which is confirmed and published, not a proposal:
| Date | Change | Position as of July 2026 |
|---|---|---|
| 2 March 2025 | National classes (BS 476 series) removed for reaction to fire and roofs; sprinkler and compartmentation changes for new care homes | In force |
| 30 September 2026 | Second common staircase required in new residential buildings with a storey over 18m (18-month transition from application deposit) | Commences this September |
| 2 September 2029 | National classification system (BS 476) removed for fire resistance — including BS 476-22 for fire doors (6-month transition from application deposit) | Confirmed and published; not yet in force |
The transition works on building control applications: work covered by an application deposited before a commencement date benefits from the stated transition period, after which the new guidance applies. In the circular's words, the update "removes the national classification system (BS 476) for fire resistance from Approved Document B" with effect from 2 September 2029.
One important nuance: design codes are moving ahead of the regulations. BS 9991:2024, the fire safety design code for residential buildings published in November 2024, already specifies fire doors by EN 13501-2 classification including smoke performance. For new residential design work following that code, the European era has effectively begun — three years before the Approved Document B deadline.
Does the 2029 phase-out make existing fire doors illegal?
No. Approved Document B is guidance for new building work. The 2029 change means that fire resistance for work approved under the Building Regulations will need European classification evidence; it does not retrospectively condemn doors already in service. The BWF Fire Door Alliance puts it plainly: "there is no need to replace fit-for-purpose fire doors that comply with the British Standard."
Existing doors continue to be governed by the occupied-building regime: the fire risk assessment and the maintenance duty under Article 17 of the Regulatory Reform (Fire Safety) Order 2005, plus — in residential buildings over 11m in England — the routine checks required by Regulation 10 of the Fire Safety (England) Regulations 2022 (communal fire doors at least every three months, flat entrance doors at least every twelve months on a best-endeavours basis). A well-maintained BS 476-tested door that passes its checks remains a compliant fire door.
Where the change does bite is on replacement and new supply as 2029 approaches: manufacturers are re-testing ranges to EN 1634-1, and legacy designs supported only by BS 476-22 evidence will progressively drop out of new work in England.
What should specifiers do today?
The sensible strategy in 2026 is to specify for where the regime is going, not where it has been. Every doorset we supply will carry third-party certification, and our advice to specifiers follows the same logic: buy evidence, not assertions.
- Prefer EN evidence for new projects. Specify the classification you need to BS EN 13501-2 — for example E30 Sa, E60 S200 or EI30 — especially for residential work designed to BS 9991:2024 and any project that could complete near or after September 2029.
- Decide deliberately between E and EI. Check the fire strategy: if insulation performance is required, say EI and require EN classification reports; if integrity is sufficient, do not over-specify EI where the market and the strategy support E.
- Ask for the classification report and field of application, not just a certificate number. The field of application tells you whether your sizes, glazing, hardware and frame details are actually covered.
- Use third-party certificated doorsets (for example Certifire, BM TRADA Q-Mark or IFC schemes) and confirm the certification scope includes the EN test route where you need it.
- Keep the evidence. File test and classification reports, certificates and the installation records with the Regulation 38 fire safety information and, on higher-risk buildings, the golden thread.
- For existing buildings, do not panic-replace. BS 476-22 evidence remains valid for doors in service; let the fire risk assessment and inspection findings — not the 2029 date alone — drive replacement decisions.
Frequently asked questions
Is BS 476 being withdrawn for fire doors?
Yes, in stages. Approved Document B in England removes the BS 476 national fire resistance classes — including BS 476-22 for fire doors — from 2 September 2029, with a six-month transition tied to building control application dates. From then, BS EN 1634-1 testing classified to BS EN 13501-2 is the sole route for new work.
Is FD30 the same as E30?
They are working equivalents: both denote 30 minutes of integrity, FD30 under BS 476-22 and E30 under BS EN 13501-2 via EN 1634-1 testing. But the EN test is generally more onerous, so an FD30 design cannot claim E30 without EN test evidence — the equivalence is indicative, not a conversion.
Is FD30 the same as EI30?
No. FD30 demonstrates 30 minutes of integrity only, while EI30 additionally requires insulation — the mean temperature rise on the unexposed face must stay within 140°C. EI is a stricter criterion, so a specification calling for EI30 can only be met with EN 1634-1 evidence classified EI30, never with an FD30 rating.
What is the difference between E, EI and EW fire doors?
E means integrity only: the door blocks flames and hot gases. EW adds radiation control, limiting radiated heat to 15 kW/m² measured 1m from the door. EI adds full insulation, limiting the temperature rise of the unexposed face. EI is the strictest of the three; the number after each class gives the minutes achieved.
What do Sa and S200 mean on a fire door classification?
They are smoke control classes under BS EN 13501-2, tested to BS EN 1634-3. Sa limits smoke leakage at ambient temperature; S200 limits leakage at both ambient temperature and 200°C, a tougher medium-temperature condition. They correspond to the UK's 's' suffix, so FD30s broadly maps to E30 Sa or E30 S200.
Do my existing BS 476-tested fire doors need replacing before 2029?
No. Approved Document B applies to new building work, and the BWF Fire Door Alliance confirms there is no need to replace fit-for-purpose fire doors tested to the British Standard. Existing doors are governed by your fire risk assessment, the Article 17 maintenance duty and, in residential buildings over 11m, Regulation 10 routine checks.
Which testing standard should I specify for a new project in 2026?
Specify the European route where you can: BS EN 1634-1 evidence classified to BS EN 13501-2, stating the class you need, such as E30 Sa or EI60. BS 9991:2024 already requires EN classifications for new residential design, and any project completing near September 2029 risks obsolete evidence if it relies on BS 476-22 alone.
What is the difference between EI1 and EI2?
Both limit the mean temperature rise on the unexposed door face to 140°C, but they differ in thermocouple positions near the edges and frame and in the maximum local rises allowed. EI1 is the stricter variant; EI2 is the classification normally used for fire doorsets in the UK and Europe. Check which one your specification cites.
- GOV.UK — Fire safety: Approved Document B
- GOV.UK — Approved Document B amendments circular: new updates to support enhanced fire safety
- BWF Fire Door Alliance — What the shift to the European fire door testing standard means for fire safety professionals
- BWF Fire Door Alliance — What is certification?
- UK Testing & Certification — Understanding BS EN 1634-1: fire resistance tests guide
- EBD Steel Doors — Understanding E, EW and EI fire door classifications