FD30 vs FD120: which fire door rating do you need?

In short

FD30 and FD120 are both certified fire doorsets, rated to resist fire for at least 30 and 120 minutes of integrity respectively (broadly E30 and Per certified design under BS EN 13501-2). The difference is duration: FD120 holds the line for 120 minutes where FD30 holds it for 30. FD30 is specified for flat entrances, HMO and escape-route doors, corridors and most internal fire doors; FD120 for major compartment walls, basements and high-hazard storage and process areas. The correct rating for any opening comes from the building's fire strategy and risk assessment, not a general rule.

30MINFD30integrity (E)
120MINFD120integrity (E)

FD30 vs FD120 at a glance

FD30FD120
Fire resistance30 minutes120 minutes
EN classification≈ E30 (integrity)Per certified design
Typical leafTypically 44 mmPer certified design
Where it is specifiedflat entrances, HMO and escape-route doors, corridors and most internal fire doorsmajor compartment walls, basements and high-hazard storage and process areas

When FD30 is the right choice

Specify FD30 where the fire strategy calls for 30minutes' integrity — flat entrances, HMO and escape-route doors, corridors and most internal fire doors. Stepping up to a higher rating than the strategy requires adds cost and weight without adding compliance; the rating should match the assessed risk at each opening.

When to step up to FD120

FD120 is specified where the fire strategy or Approved Document B demands 120 minutes rather than 30major compartment walls, basements and high-hazard storage and process areas. At this rating the doorset construction is heavier and, above FD60, the design and glazing become more restricted; confirm what is achievable against the certified field of application.

Both figures describe integrity (E) — resisting flame and hot gases — not insulation (EI), which limits heat transfer and is separately tested. Leaf thicknesses are typical, not mandatory; the certified design governs. Also see FD30 vs FD60, the full range (FD30–FD120), or run the compliance checker.